PVSP-156H-N610~N625M10
1575Xem chi tiết

Applicable scope and purpose
● Short -circuit protection
● Over-load protection
● Control
● Isolation
● DC system protection
NDB2T-63 (UL489) được thiết kế dành riêng cho hệ thống phân phối điện áp thấp trong các lĩnh vực công nghiệp, tòa nhà, năng lượng, viễn thông và hạ tầng.
Main technical specification
● Electrical parameters
○ Rated working voltage and relevant breaking capacity:
| Pole | 1P | 2P | 3P | 1P | 2P | 3P | |
| Rating current | 1~32A | 35~63A | |||||
| Item | Icu | ||||||
| Voltage | AC 120V | 10kA | — | — | 10kA | — | — |
| AC 240V | — | 10kA | 10kA | — | 10kA | 10kA | |
| AC 277V | 10kA | — | — | — | — | — | |
| AC 480Y/277V | — | 10kA | 10kA | — | — | — | |
| DC60V | 10kA | 10kA | — | 10kA | 10kA | — | |
| DC125V | — | 10kA | — | — | 10kA | — | |
○ Impulse withstand test voltages: 4kV
○ electrical endurance: 10000 times;Mechanical endurance: 20000 times
● Product certification and implementation standard.:
○ Product certificate:UL489;
○ Product certification standard:UL489;
● Environmental requirements:RoHS
● Isolation function
○ Practical breaking instructions
○ View window within the green identification said contact in the off position
● Tripping characteristic B type curve
○ Protection of short circuit current small load
○ rated current:1A~63A
○ tripping characteristic:The instantaneous tripping range 4In(1±20%) C type curve
○ Protect normal load and distribution wire cable
○ rated current:1A~63A
○ tripping characteristic:The instantaneous tripping range 8In(1±20%) D type curve
○ Protect starting current big impact load(Such as motor, transformer)
○ rated current:1A~63A
○ tripping characteristic:The instantaneous tripping rang 12In(1±20%)
5、Normal working environment
● Ambient temperature:-40℃~+70℃
● Air relative humidity:≤95%
● Altitude:≤2000m
● pollution degree: 3
● Service place without significant vibration and impact
● Lower capacity coefflcient table above 2000 meters above sealevel

● Side-by-side volume reduction coefflcient table

6. Tripping characteristic

7、Outline dimensions

3P
8、Mounting
Modular construction,can be installed in EN60715 TH 35mm x 7.5mm standard guide rail.
9、Connect line requirements
○ Standard cross-sections of round copper conductors: 1~35mm2
○ Terminal screw: M5 ,Rated torque : 2.0N.m
11 、 Notice
1、Customers who disassemble the product without approval shall undertake relevant quality problems by themselves;
2、Do not touch the naked part of conductive components when the product is power on;
3、Don’t test characteristics of the breaker optionally, the manufacturer is irresponsible for such quality problems;
4、Keep wiring correct to prevent malfunction or damage of wiring terminals.
5、Please open the cover when installing the accessory. Please refer to OF2, SD2, MX+OF2 Instruction for details.
1. Applicable Scope and Purpose The NDQ3-630 P-grade ATSE are applicable for sites with the AC voltage below AC380V.AC400V.AC415V and the rated frequency of 50Hz. This product complies with the GB14048.1-2012 and GB/T14048.11-2016 standards i...
Xem chi tiếtApplications: The NDG3V-250~800 series switch-disconnectors are applicable to electric systems with a rated voltage up to DC 1500V and a rated current up to 800A. It can be used for infrequent close and open, it provides isolation and breaking ...
Xem chi tiếtApplications: NDGR2-160 isolating switch fuse group applied to ac 50 hz, rated voltage of AC400V, AC690V, rated current 160 a low-voltage distribution network, or motor as infrequently connected, breaking circuit and circuit isolation...